Re: It's said that induction fans (draft inducers) increase efficiency
FYI - I didn't see Nick's post until Roger quoted it. Nick's post
didn't show up on the NNTP server I use.
Nick Wrote:
> That might reduce the cold air leakage into the house by a few
> cfm, since the furnace would not pull combustion air out of
> the house, but how would it increase efficiency? Starting with
> outdoor air at say, 30 F, we can either heat it to 70 F in the
> house, then heat it up to the flue gas temp, or heat it from
> 30 to the flue gas temp in one step, with the same energy, no?
I'm thinking that AFUE ratings include or take into account the degree
to which a furnace prevents outside air leakage into a house, hence
any furnace that is designed for a closed intake and combustion path
would result in a higher AFUE rating.
The point is not that you are using cold outside air vs warm inside
air for combustion.
The point is that by having a closed intake and exhaust pathway you
eliminate the furnace as a point where outside air can enter the
house, or that household air can leave the house (via the flue).
Roger wrote:
> Yes and no - A triple wall pipe, which preheats the air with
> the otherwise wasted heat from the flue gas is more efficient.
Yes, and that is another modification that can be made to an original
low-efficiency furnace.
> If you use a mechanism to stop the air up the flue during the
> off cycle, it can still be more efficient in a back-handed
> sort of way,
I don't think that any such mechanism is necessary.
If you have a furnace where the combustion intake has been sealed such
that it can only draw air from the outside, and naturally the flue is
sealed so that it exhausts out the chimney, then you've got no reason
to close that pathway when the furnace is off.
You've got no reason to close it because the only reason to close it
is if you have a high, natural ambient airflow through the intake and
out the flue. The distance from the exterior opening of the intake
and the top of the chimney is probably no more than 15 or 20 feet, and
they would be on the same side of the house. Unless the geometry of
the house is very unusual, they would both experience the same ambient
air pressure, so you'd expect to get little or no net airflow from
intake to exhaust.
If in a given situation you actually would benefit from a damper
mechanism, then I'd be afraid that when it's open that you'd have way
too much air entering the intake for normal combustion during heating
(when the damper mechanism would be open).
|