Re: It's said that induction fans (draft inducers) increase
Don Ocean wrote:
>
> Any bets on it passing a UL inspection.. (etc)
I don't have to get it inspected. I don't need a permit. I'll never
get a fine.
Put that in your furnace and smoke it.
>
> I wonder if the Fire Marshal would agree with you.
The Fire Marshall is out of the picture.
>
> Much easier to tune properly..
They (mostly) don't have primary air adjustment shutters. So how do
you tune them?
> hard to clog and stays pretty much the same throughout
> the life sapm
But they don't heat the heat exchanger galley as evenly as long,
slotted up-shot burners.
> .. Slot burners suffer many maladies.
Like what - like maybe pull them out and give them a shake every 5
years?
> And yes inshots are more efficient..especially with a good
> secondary heat exchanger.
Anything is bound to be more efficient with a second heat exchanger.
>
> Then your a fool.. Flex rots and cracks.
For combustion intake?
Cold air, hardly any pressure or measurable flow?
Even if they "rot" and "crack", worst that can happen is that the
furnace starts sucking intake combustion air from around the furnace -
something it would normally do anyways.
>
> It is in an outside environment that has been piped in.
There is already a supply duct running down into the furnace room from
an outside vent about 5 ft above grade. The bottom of the duct was
open - allowing outside air to flood into the furnace room. I closed
off the bottom of the duct and ran 4 flex lines (4") from the duct to
the furnace cabinet (2 for the primary combustion air and 2 for draft
air).
> Simple grade school physics.
Yup, it sure is.
|