Electric water boiler recommendations
|
|
| Geoman1 2005-10-24, 3:21 pm |
| I have a commercial customer who desires a Unico system with a heat pump and
hot water coil for auxiliary heat. Its cheaper to heat the water with
electric here than with gas.
I have no past experience with the brands of electric boilers, they have not
been promoted well in our area, so suggestions and past experiences would be
greatly appreciated.
Single phase 208/230
93,200 btu max, staging is desirable
Possibly Four (4) zones on this system.
Thanks,
Rich
| |
| Steve Scott 2005-10-24, 4:21 pm |
| Best place to ask would be on The Wall.
On Mon, 24 Oct 2005 13:42:13 -0400, "Geoman1" <Geo1> wrote:
>I have a commercial customer who desires a Unico system with a heat pump and
>hot water coil for auxiliary heat. Its cheaper to heat the water with
>electric here than with gas.
>
>I have no past experience with the brands of electric boilers, they have not
>been promoted well in our area, so suggestions and past experiences would be
>greatly appreciated.
>
>Single phase 208/230
>93,200 btu max, staging is desirable
>
>Possibly Four (4) zones on this system.
>
>Thanks,
>Rich
>
--
The mass of mankind was not born with
saddles on their backs, nor a favored
few booted and spurred, ready to ride
them legitimately, by the grace of God.
| |
| Geoman1 2005-10-24, 5:21 pm |
|
"Steve Scott" <sscott1@twcny.rr.com> wrote in message
news:mrbql157rn5n4c637hpnu4b37i6rr6c42m@4ax.com...
> Best place to ask would be on The Wall.
>
> On Mon, 24 Oct 2005 13:42:13 -0400, "Geoman1" <Geo1> wrote:
>
>
>
> --
> The mass of mankind was not born with
> saddles on their backs, nor a favored
> few booted and spurred, ready to ride
> them legitimately, by the grace of God.
Not sure what The Wall is :-)
Rich
>
>
>
| |
| Tekkie® 2005-10-24, 6:30 pm |
| posted for all of us...
I don't top post - see either inline or at bottom.
>
> Not sure what The Wall is :-)
> Rich
>
Well, it ain't in Berlin no more. Could be in China. But I think it's what
Stumped hits his head against...
--
My boss said I was dumb and apathetic.
I said I don't know and I don't care...
Tekkie
| |
| Geoman1 2005-10-24, 6:30 pm |
|
"Tekkie®" <Tekkie@comcast.net> wrote in message
news:kvidndKIr6mI1MDenZ2dnUVZ_s-dnZ2d@comcast.com...
> posted for all of us...
> I don't top post - see either inline or at bottom.
>
> Well, it ain't in Berlin no more. Could be in China. But I think it's
> what
> Stumped hits his head against...
> --
> My boss said I was dumb and apathetic.
> I said I don't know and I don't care...
>
> Tekkie
Tekkie, you don't know how funny your post is. I live in a town called
Berlin!! You had me so darn confused until I realized you were talking
about Germany!
Rich
| |
| gofish@gonefishin.net 2005-10-24, 7:21 pm |
| On Mon, 24 Oct 2005 16:54:14 -0400, "Geoman1" <Geo1> wrote:
>
>"Tekkie®" <Tekkie@comcast.net> wrote in message
>news:kvidndKIr6mI1MDenZ2dnUVZ_s-dnZ2d@comcast.com...
>
>Tekkie, you don't know how funny your post is. I live in a town called
>Berlin!! You had me so darn confused until I realized you were talking
>about Germany!
>
>
>Rich
>
>
heres the link to The Wall.....you need Rich.... http://www.heatinghelp.com/
| |
| Oscar_Lives 2005-10-24, 10:21 pm |
|
"Geoman1" <Geo1> wrote in message
news:FeqdnesOr4sBrsDeRVn-uQ@adelphia.com...
>
> "Steve Scott" <sscott1@twcny.rr.com> wrote in message
> news:mrbql157rn5n4c637hpnu4b37i6rr6c42m@4ax.com...
>
>
> Not sure what The Wall is :-)
> Rich
Try www.pinkfloyd.com
| |
| HeatMan 2005-10-24, 11:21 pm |
| Burnham Carefree electric boiler. 68K is the largest they have listed, but
you can get 2 slightly smaller ones and break it up on a per zone basis.
"Geoman1" <Geo1> wrote in message
news:ao6dna1hKfRugcDeRVn-qQ@adelphia.com...
> I have a commercial customer who desires a Unico system with a heat pump
and
> hot water coil for auxiliary heat. Its cheaper to heat the water with
> electric here than with gas.
>
> I have no past experience with the brands of electric boilers, they have
not
> been promoted well in our area, so suggestions and past experiences would
be
> greatly appreciated.
>
> Single phase 208/230
> 93,200 btu max, staging is desirable
>
> Possibly Four (4) zones on this system.
>
> Thanks,
> Rich
>
>
| |
|
|
| Steve Scott 2005-10-25, 12:21 am |
| www.heatinghelp.com look to the left banner for The Wall. Great bunch
of wet heads there.
On Mon, 24 Oct 2005 15:18:54 -0400, "Geoman1" <Geo1> wrote:
>
>"Steve Scott" <sscott1@twcny.rr.com> wrote in message
>news:mrbql157rn5n4c637hpnu4b37i6rr6c42m@4ax.com...
>
>
>Not sure what The Wall is :-)
>Rich
>
>
--
The mass of mankind was not born with
saddles on their backs, nor a favored
few booted and spurred, ready to ride
them legitimately, by the grace of God.
| |
| Geoman1 2005-10-25, 1:21 am |
| Thanks Fish, Heatman and Steve. I sincerely appreciate your help concerning
this.
As I have said many times in the past, this is the greatest group of guys
and one gal on the net!
Thanks again
Rich
"HeatMan" <heatair@NOSPAM.yahoo.com> wrote in message
news:NKf7f.5152$NJ.974@bignews7.bellsouth.net...
> Burnham Carefree electric boiler. 68K is the largest they have listed,
> but
> you can get 2 slightly smaller ones and break it up on a per zone basis.
>
>
> "Geoman1" <Geo1> wrote in message
> news:ao6dna1hKfRugcDeRVn-qQ@adelphia.com...
> and
> not
> be
>
>
|
|
|
|
|