|
Home > Archive > Home Repair forum > November 2005 > AFCI Fuse - is so annoying
You are viewing an archived Text-only version of the thread.
To view this thread in it's original format and/or if you want to reply to
this thread please [click here]
| Author |
AFCI Fuse - is so annoying
|
|
| Zean Smith 2005-11-09, 6:21 pm |
| My house which is 1.5 years old has been having problem with the Siemens
AFCI Fuse. According to the builder, this fuse is installed on 2nd floor
for bedrooms for some reasons. The AFCI part of the fuse always get tripped
after power interruption by local hydro company. I had to manually went to
basement to reset it.
This AFCI is so stupid and annoying. It has been raining these days these
days and it almost got tripped once a week! Never had any problem usually in
sunny days because there is no power interruption.
1. Is it possible to replace it with the regular Fuse? I am really sick of
this. Will that violate the electrical code??
2. This is so annoying that I even tried to unplug computers, light fixture
but didn't help, still got same problem. Any other suggestions?
3. Should get another AFCI Fuse? maybe the one I have is defected??
Help....
| |
| Jeff Wisnia 2005-11-09, 6:21 pm |
| Zean Smith wrote:
> My house which is 1.5 years old has been having problem with the Siemens
> AFCI Fuse. According to the builder, this fuse is installed on 2nd floor
> for bedrooms for some reasons. The AFCI part of the fuse always get tripped
> after power interruption by local hydro company. I had to manually went to
> basement to reset it.
>
> This AFCI is so stupid and annoying. It has been raining these days these
> days and it almost got tripped once a week! Never had any problem usually in
> sunny days because there is no power interruption.
>
> 1. Is it possible to replace it with the regular Fuse? I am really sick of
> this. Will that violate the electrical code??
> 2. This is so annoying that I even tried to unplug computers, light fixture
> but didn't help, still got same problem. Any other suggestions?
> 3. Should get another AFCI Fuse? maybe the one I have is defected??
>
> Help....
>
>
What you are calling a fuse is likely what informed folks in the USA
wuld call a circuit breaker, in your case it's an Arc Fault Circuit
Interrupter (AFCI) type.
It's becoming code required for new construction to prevent things like
squashed extension cords from creating holocausts, they "open" when they
sense a spikey current flow through them, as occurs from an arcing
crushed cord.
I'd suggest that you not replace it with a regular breaker, for safety's
sake plus if something bad did happen and an inspector found what you'd
done, insurance might not pay for the damage.
Have you tried consulting with the power company and/or Seimens to see
if there's a cure for what your encountering?
Will it trip if you turn your main circuit breaker off and on, or does
it just happen when the power company has problems?
Let us know what you find out, I for one am interested in learning more
about those AFCIs.
HTH,
Jeff
--
Jeffry Wisnia
(W1BSV + Brass Rat '57 EE)
"Truth exists; only falsehood has to be invented."
| |
|
| These are first generation AFCI devices. As with a lot of new technology,
there are often problems with early models. If it wasn't to much of a
bother, I'd wait for newer generation units before replacing it. It would be
a violation of NEC to replace it with a non AFCI unit
"Zean Smith" <nospam@nospamaaamail.com> wrote in message
news:8PednXe_scqb7-_eRVn-rg@rogers.com...
> My house which is 1.5 years old has been having problem with the Siemens
> AFCI Fuse. According to the builder, this fuse is installed on 2nd floor
> for bedrooms for some reasons. The AFCI part of the fuse always get
> tripped after power interruption by local hydro company. I had to manually
> went to basement to reset it.
>
> This AFCI is so stupid and annoying. It has been raining these days these
> days and it almost got tripped once a week! Never had any problem usually
> in sunny days because there is no power interruption.
>
> 1. Is it possible to replace it with the regular Fuse? I am really sick of
> this. Will that violate the electrical code??
> 2. This is so annoying that I even tried to unplug computers, light
> fixture but didn't help, still got same problem. Any other suggestions?
> 3. Should get another AFCI Fuse? maybe the one I have is defected??
>
> Help....
>
| |
| Goedjn 2005-11-09, 7:21 pm |
| [color=darkred]
Yes, you can replace it with a regular breaker, and yes,
doing so will violate code.
You might be able to get some sort of device for your
house main that shuts the power off when it goes out,
and resets itself only after getting clean power for
an arbitrary period of time.
| |
|
| You use the term "hydro" when referring to the electricity utility, that
means you are in Ontario, or Quebec, Canada. If you are in Ontario, it would
be against the electrical code to remove it. I don't know about Quebec, they
do things differently, but usually before Ontario mandates things.
"Zean Smith" <nospam@nospamaaamail.com> wrote in message
news:8PednXe_scqb7-_eRVn-rg@rogers.com...
> My house which is 1.5 years old has been having problem with the Siemens
> AFCI Fuse. According to the builder, this fuse is installed on 2nd floor
> for bedrooms for some reasons. The AFCI part of the fuse always get
tripped
> after power interruption by local hydro company. I had to manually went to
> basement to reset it.
>
> This AFCI is so stupid and annoying. It has been raining these days these
> days and it almost got tripped once a week! Never had any problem usually
in
> sunny days because there is no power interruption.
>
> 1. Is it possible to replace it with the regular Fuse? I am really sick of
> this. Will that violate the electrical code??
> 2. This is so annoying that I even tried to unplug computers, light
fixture
> but didn't help, still got same problem. Any other suggestions?
> 3. Should get another AFCI Fuse? maybe the one I have is defected??
>
> Help....
>
>
| |
| thrugoodmarshall@hotmail.com 2005-11-10, 11:21 am |
| My house (which is just about 1 year old; moved in August 2004) had
AFCIs.
Tons of nuisance trips, especially when powering off an inductive load
(ceiling fan). Code requires them for all the bedrooms.
I talked to the Siemens rep at a trade show (I do industrial electrical
controls). He hemmed & hawed & suggested I take it back for a new one.
I talked to some electricians (house wiring folks; not plant (factory)
electricians), and the general consensus is that they're worthless due
to nuisance trips.
They've been required in receptacles since Jan1, 2002. They're
required in bedrooms only, and they're intended to protect against
fires started by arcing (short to ground).
Some background on why and when these are required:
>From the consumer products safety commission:
http://www.cpsc.gov/LIBRARY/FOIA/FOIA03/os/ecafci.pdf
And, from underwriters laboratories:
http://www.ul.com/regulators/ode/0504.pdf
I suggest you look into the risks and make an informed decision for
yourself.
Personally, I believe that in my house, my decision supersedes code
requirements. It's my house, dammit. I reviewed the risks, and
evaluated the nuisance costs to my wife and myself, and then removed
them and installed regular breakers.
Zean Smith wrote:
> My house which is 1.5 years old has been having problem with the Siemens
> AFCI Fuse. According to the builder, this fuse is installed on 2nd floor
> for bedrooms for some reasons. The AFCI part of the fuse always get tripped
> after power interruption by local hydro company. I had to manually went to
> basement to reset it.
>
> This AFCI is so stupid and annoying. It has been raining these days these
> days and it almost got tripped once a week! Never had any problem usually in
> sunny days because there is no power interruption.
>
> 1. Is it possible to replace it with the regular Fuse? I am really sick of
> this. Will that violate the electrical code??
> 2. This is so annoying that I even tried to unplug computers, light fixture
> but didn't help, still got same problem. Any other suggestions?
> 3. Should get another AFCI Fuse? maybe the one I have is defected??
>
> Help....
| |
| thrugoodmarshall@hotmail.com 2005-11-10, 11:21 am |
| arcing (short to ground)
sorry, that's not what AFCI is for; that's just the first thing that
came to mind when I though ARC. My bad!
Short-to-ground is protected by a regular breaker. You'll get nice fat
spark if you do this, but you don't need AFCI to detect it.
AFCI tries to detect all the other types of arc that don't trip an
overcurrent breaker.
They accomplishing this by watching the waveform and figuring out what
a bad arc looks like.
They actually have an algorithm (computer program) to detect this.
Again, from the consumer products safety commission:
http://www.cpsc.gov/volstd/afci/AFCIFireTechnology.pdf
Again, sorry for the sloppy (wrong) definition of arc earlier!
| |
| Percival P. Cassidy 2005-11-10, 11:21 am |
| A year or more ago I replaced a regular breaker by an AFCI breaker in a
bedroom circuit in our 30-yr-old house, and it's never tripped once.
This is a Cutler-Hammer CH panel and breaker. Perhaps Siemens hasn't yet
figured out how to build them right.
Perce
On 11/10/05 09:31 am thrugoodmarshall@hotmail.com tossed the following
ingredients into the ever-growing pot of cybersoup:
> My house (which is just about 1 year old; moved in August 2004) had
> AFCIs.
>
> Tons of nuisance trips, especially when powering off an inductive load
> (ceiling fan). Code requires them for all the bedrooms.
>
> I talked to the Siemens rep at a trade show (I do industrial electrical
> controls). He hemmed & hawed & suggested I take it back for a new one.
>
> I talked to some electricians (house wiring folks; not plant (factory)
> electricians), and the general consensus is that they're worthless due
> to nuisance trips.
>
> They've been required in receptacles since Jan1, 2002. They're
> required in bedrooms only, and they're intended to protect against
> fires started by arcing (short to ground).
>
> Some background on why and when these are required:
> http://www.cpsc.gov/LIBRARY/FOIA/FOIA03/os/ecafci.pdf
>
> And, from underwriters laboratories:
> http://www.ul.com/regulators/ode/0504.pdf
>
> I suggest you look into the risks and make an informed decision for
> yourself.
>
> Personally, I believe that in my house, my decision supersedes code
> requirements. It's my house, dammit. I reviewed the risks, and
> evaluated the nuisance costs to my wife and myself, and then removed
> them and installed regular breakers.
[color=darkred]
| |
| kevin 2005-11-10, 11:21 am |
| Yikes. You lose power once a week? What's wrong with your utility
company? Many parts of even rural West Africa aren't that unreliable.
-Kevin
| |
| John Grabowski 2005-11-10, 1:21 pm |
| I seem to recall reading an article in one of the trade magazines that
mentioned earlier versions of the AFCI circuit breakers were subjected to
nuisance trips. If this is the case, you might want to replace yours with a
brand new one. There is the possibility that it is not nuisance tripping
and that there is something genuinely wrong with your wiring. If you
install a new one and have the same problem, call an electrician.
"Zean Smith" <nospam@nospamaaamail.com> wrote in message
news:8PednXe_scqb7-_eRVn-rg@rogers.com...
> My house which is 1.5 years old has been having problem with the Siemens
> AFCI Fuse. According to the builder, this fuse is installed on 2nd floor
> for bedrooms for some reasons. The AFCI part of the fuse always get
tripped
> after power interruption by local hydro company. I had to manually went to
> basement to reset it.
>
> This AFCI is so stupid and annoying. It has been raining these days these
> days and it almost got tripped once a week! Never had any problem usually
in
> sunny days because there is no power interruption.
>
> 1. Is it possible to replace it with the regular Fuse? I am really sick of
> this. Will that violate the electrical code??
> 2. This is so annoying that I even tried to unplug computers, light
fixture
> but didn't help, still got same problem. Any other suggestions?
> 3. Should get another AFCI Fuse? maybe the one I have is defected??
>
> Help....
>
>
| |
| Goedjn 2005-11-10, 1:21 pm |
| On Thu, 10 Nov 2005 09:44:54 -0500, "Percival P. Cassidy"
<Nobody@NotMyISP.net> wrote:
>A year or more ago I replaced a regular breaker by an AFCI breaker in a
>bedroom circuit in our 30-yr-old house, and it's never tripped once.
>
>This is a Cutler-Hammer CH panel and breaker. Perhaps Siemens hasn't yet
>figured out how to build them right.
>
From the OP's description, the breakers are tripping because
they *ARE* detecting an arc fault, only on the supply side
instead of the load side.
| |
| gfretwell@aol.com 2005-11-10, 2:21 pm |
| On 10 Nov 2005 06:41:53 -0800, thrugoodmarshall@hotmail.com wrote:
>arcing (short to ground)
>sorry, that's not what AFCI is for; that's just the first thing that
>came to mind when I though ARC. My bad!
>
>Short-to-ground is protected by a regular breaker. You'll get nice fat
>spark if you do this, but you don't need AFCI to detect it.
>
>AFCI tries to detect all the other types of arc that don't trip an
>overcurrent breaker.
>
>They accomplishing this by watching the waveform and figuring out what
>a bad arc looks like.
>
>They actually have an algorithm (computer program) to detect this.
>
>Again, from the consumer products safety commission:
>http://www.cpsc.gov/volstd/afci/AFCIFireTechnology.pdf
>
>Again, sorry for the sloppy (wrong) definition of arc earlier!
An AFCI will also trip when it sees a neutral to ground short. That is
part of the GFP protection (30ma GFCI)
This usually happens in that big cludge box in the ceiling and gets
blamed on the fan. I would knock gently on any ceiling fixture bell or
fan bells and see if you can cause a trip. If so open up the box and
put a wrap of tape on the wirenuts. I bet there is a little exposed
wire on the neutral. That never bothered anything until we started
looking at ground faults.
| |
| Chip C 2005-11-10, 3:21 pm |
|
Zean Smith wrote:
> My house which is 1.5 years old has been having problem with the Siemens
> AFCI Fuse. According to the builder, this fuse is installed on 2nd floor
> for bedrooms for some reasons. The AFCI part of the fuse always get tripped
> after power interruption by local hydro company. I had to manually went to
> basement to reset it.
>
> This AFCI is so stupid and annoying. It has been raining these days these
> days and it almost got tripped once a week! Never had any problem usually in
> sunny days because there is no power interruption.
>
> 1. Is it possible to replace it with the regular Fuse? I am really sick of
> this. Will that violate the electrical code??
> 2. This is so annoying that I even tried to unplug computers, light fixture
> but didn't help, still got same problem. Any other suggestions?
> 3. Should get another AFCI Fuse? maybe the one I have is defected??
>
> Help....
A while ago in this NG someone posted that at their work, AFCI's (which
had been installed everywhere in some ill-conceived scheme) routinely
tripped whenever anyone plugged in a fluorescent desk lamp that was
switched on. The same would probably apply to having the power come on
with the same kind of lamp plugged in. So for point 2 above, did you
unplug everything before the power came back on? I'd try that.
Chip C
| |
| wkearney99 2005-11-11, 11:21 am |
| > Personally, I believe that in my house, my decision supersedes code
> requirements. It's my house, dammit. I reviewed the risks, and
> evaluated the nuisance costs to my wife and myself, and then removed
> them and installed regular breakers.
Then, personally, you'll have no one but yourself to blame when the house
burns down and kills your family in the process because you wanted to
circumvent code. Oh and the insurance company will doubtless tell you to
sod off on any claims you might want to make. So g'head and replace it,
you'll only risk being homeless, broke and alone.
| |
| wkearney99 2005-11-11, 11:21 am |
| > Yikes. You lose power once a week? What's wrong with your utility
> company? Many parts of even rural West Africa aren't that unreliable.
Pfft, try suburban DC. Pepco can't keep power running without interruption
for more than a week.
| |
| some user 2005-11-11, 11:21 am |
|
"wkearney99" <wkearney99@hotmail.com> wrote in message
news:u6udnSh-VIBlMeneRVn-uA@speakeasy.net...
>
> Then, personally, you'll have no one but yourself to blame when the house
> burns down and kills your family in the process because you wanted to
> circumvent code. Oh and the insurance company will doubtless tell you to
> sod off on any claims you might want to make. So g'head and replace it,
> you'll only risk being homeless, broke and alone.
>
This kind of comments are annoying. Few of homes, except the very new ones,
use AFCI. My home, built in 2000, has none. Are you saying most of us are
really in danger of buring alive because we don't have AFCI?
I bet you are much more likely to die in an auto accident, earth quake, or
even
fall from your bed, then from lack of AFCI.
| |
|
|
|
|
|