Home > Archive > Home Repair forum > April 2006 > Old Ceiling Fan/Light gone with two wires coming from the ceiling
You are viewing an archived Text-only version of the thread.
To view this thread in it's original format and/or if you want to reply to
this thread please [click here]
| Author |
Old Ceiling Fan/Light gone with two wires coming from the ceiling
|
|
|
| There was an old ceiling fan/light with a pull chain in which I took
off a week ago. There is a switch in the wall that also controls the
light. When I connected the new light wires (no fan - two 60 watt
bulbs) to the fixtures light wires (two old wires look the same) and
the wall switch wires (14/2) and turned the power on, the ceiling light
bulbs stayed on all the time when the wall switch is off. When I
turned the wall switch on it tripped the breaker in the downstairs
panel.
There were only two wires coming from the ceiling, so I figured one was
hot and one was neutral. Maybe, they were connected to the outlet in
the wall?
Any ideas how I miswired this light?
| |
|
| CJ wrote:
> There was an old ceiling fan/light with a pull chain in which I took
> off a week ago. There is a switch in the wall that also controls the
> light. When I connected the new light wires (no fan - two 60 watt
> bulbs) to the fixtures light wires (two old wires look the same) and
> the wall switch wires (14/2) and turned the power on, the ceiling light
> bulbs stayed on all the time when the wall switch is off. When I
> turned the wall switch on it tripped the breaker in the downstairs
> panel.
>
> There were only two wires coming from the ceiling, so I figured one was
> hot and one was neutral. Maybe, they were connected to the outlet in
> the wall?
>
> Any ideas how I miswired this light?
>
If I am reading right you have wired:
--------------------------O------------------------
"fixture light wires" | to switch
(power supply) light
|
--------------------------O------------------------
It should be wired:
--------------------------O------------------------
"fixture light wires" to switch
(power supply)
O------------------------
|
light
|
--------------------------O
The NEC requires the top supply wire to be the hot wire (typically
black) and the bottom supply wire to be the neutral (white).
With Romex to the switch - top wire white taped/marked black, bottom
wire black.
The connections are required to be in a junction box which the light
fixture is secured to.
If this looks wrong inquire further.
bud--
| |
|
| Thanks Bud... After seeing your diagram I realized what I did wrong.
You did your good deed for a month or more.
Chris
|
|
|
|
|