Home > Archive > Home Repair forum > April 2006 > Extending the Neutral Wire for AFCI & GFCI Breakers in a Breaker Panel









You are viewing an archived Text-only version of the thread. To view this thread in it's original format and/or if you want to reply to this thread please [click here]

 

Author Extending the Neutral Wire for AFCI & GFCI Breakers in a Breaker Panel
tyneskj@gmail.com

2006-04-29, 1:21 am

I would like to install an AFCI breaker for my bedroom outlet circuit
and an GFCI breaker for my bathroom outlet circuit. The problem is
that the breakers need their respective neutral circuit wires taken
from the neutral bus bar to the new AFCI/GFCI breaker(s), but the
neutral wires are too short to reach the breakers. What kind of spices
(ie. crimp, stab or twist) could I use to extend the neutral wires that
is up to the current NEC code?

bud5489@earthlink.net

2006-04-29, 4:21 am

crimp is best

Toller

2006-04-29, 10:21 am


<tyneskj@gmail.com> wrote in message
news:1146281979.911462.236780@y43g2000cwc.googlegroups.com...
>I would like to install an AFCI breaker for my bedroom outlet circuit
> and an GFCI breaker for my bathroom outlet circuit. The problem is
> that the breakers need their respective neutral circuit wires taken
> from the neutral bus bar to the new AFCI/GFCI breaker(s), but the
> neutral wires are too short to reach the breakers. What kind of spices
> (ie. crimp, stab or twist) could I use to extend the neutral wires that
> is up to the current NEC code?
>

The best thing to do is to move your breakers around so the it can reach.
That ought to be possible.
If not, wire nuts will meet code as long as it is all done in the box.

I have the opposite problem. My wires are all so long that it is difficult
to fit them in the breaker box. I ought to trim them down, but am afraid as
soon as I do it I will need them longer for some reason. Putting a transfer
switch in was a real trip.


Tom The Great

2006-04-29, 1:21 pm

On 28 Apr 2006 20:39:39 -0700, tyneskj@gmail.com wrote:

>I would like to install an AFCI breaker for my bedroom outlet circuit
>and an GFCI breaker for my bathroom outlet circuit. The problem is
>that the breakers need their respective neutral circuit wires taken
>from the neutral bus bar to the new AFCI/GFCI breaker(s), but the
>neutral wires are too short to reach the breakers. What kind of spices
>(ie. crimp, stab or twist) could I use to extend the neutral wires that
>is up to the current NEC code?


After reading the NEC, I found the wirenuts I was finding in
customer's pannels was 100% ok, if spacing was maintained. So wire
nuts are ok, but when I retrofited my own pannel for AFCI's I used
butt splices. They look cleaner than wirenuts and are allowed.

Remember, reference the NEC, not my post, and you will see splices are
ok, and how to do them properly.

hth,

tom @ www.NoCostAds.com