OMNI Pro II Zone Secure Issue
|
|
| DeputyDawg 2005-10-30, 1:21 am |
| Hooked up 3 windows to the same Zone. To get an NOT READY ALL 3 Windows
have to be breached. How can I make it so that if only ONE is breached it
would show NOT READY? I wired all 3 together and then onto the single wire
running to the OMNI Pro II board.
| |
| jmj1492@msn.com 2005-10-30, 2:21 am |
| You'll need to wire them in series, no parallel.
| |
| Flavio Silva 2005-10-30, 2:21 am |
| **** Post for FREE via your newsreader at post.mcse.ms ****
Test
"DeputyDawg" <anyone@hotmail.com> wrote in message
news:dfc2a$43644294$ce94b4c7$28707@DIALUPUSA.NET...
Hooked up 3 windows to the same Zone. To get an NOT READY ALL 3 Windows
have to be breached. How can I make it so that if only ONE is breached it
would show NOT READY? I wired all 3 together and then onto the single wire
running to the OMNI Pro II board.
-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=
*** mcse.ms - The #1 Usenet Newsgroup Service on The Planet! ***
http://www.mcse.ms
Unlimited Download - 19 Seperate Servers - 90,000 groups - Uncensored
-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=-=
| |
| DeputyDawg 2005-10-30, 8:21 pm |
| Thanks. It did the trick.
::: You'll need to wire them in series, no parallel.
|
|
|
|