| I'm working on selecting fuses for a control circuit. My source is
460/3/60, going to a 300 VA transformer, to a fuse, a switch, then to a
motor starter.
Would this be considered a "branch circuit"?
I would like to use a time delay midget fuse, using the fuseholder mounts
that come on the transformer. However, the specs on the midget fuse say
"not designed for branch circuit use".
Thanks.
| |
| operator jay 2006-08-23, 8:25 pm |
|
"Ed" <a@a.com> wrote in message
news:c7edncybJbUH0XHZnZ2dnUVZ_sidnZ2d@rcn.net...
> I'm working on selecting fuses for a control circuit. My source is
> 460/3/60, going to a 300 VA transformer, to a fuse, a switch, then to a
> motor starter.
>
> Would this be considered a "branch circuit"?
>
> I would like to use a time delay midget fuse, using the fuseholder mounts
> that come on the transformer. However, the specs on the midget fuse say
> "not designed for branch circuit use".
>
> Thanks.
>
>
I assume the power for the motor comes from the source and not the 300VA
transformer. A control circuit would generally not be a branch circuit.
There are of course more rules for electrical installations than what you
will read on the side of a fuse. I hope you are licensed to do what you are
doing.
|
|
|
|
|