Author 3 phase vs 1 phase
jml0429@yahoo.com

2008-01-17, 5:25 pm

I have a Nordson hotmelt machine and it requires single phase 240 my
maintenance mechanic has it hooked up to a 3 phase 240 line and he
say's that will work fine. I have been having multiple electrical
problems with these machines and we have been unable to determine what
is the cause. Is it ok to leave 3 phase on single phase requirement?
phil-news-nospam@ipal.net

2008-01-17, 5:25 pm

On Thu, 17 Jan 2008 12:20:34 -0800 (PST) jml0429@yahoo.com wrote:

| I have a Nordson hotmelt machine and it requires single phase 240 my
| maintenance mechanic has it hooked up to a 3 phase 240 line and he
| say's that will work fine. I have been having multiple electrical
| problems with these machines and we have been unable to determine what
| is the cause. Is it ok to leave 3 phase on single phase requirement?

There would be 2 wires to the machine (plus EGC for protective ground).
Probably no neutral. If the incoming power is 240 delta with a center
tapped neutral on one side, connecting to the two phases that are 120
volts relative to the neutral is just fine. If it is 208Y/120 then the
machine is undervoltage and you'd be getting only about 75% of the heat
you should get.

What kinds of electrical problems are you having?

--
-----------------------------------------------------------------------------
| Phil Howard KA9WGN | http://linuxhomepage.com/ http://ham.org/ |
| (first name) at ipal.net | http://phil.ipal.org/ http://ka9wgn.ham.org/ |
-----------------------------------------------------------------------------
jmlpa

2008-01-18, 9:25 am

On Jan 17, 4:51 pm, phil-news-nos...@ipal.net wrote:
> On Thu, 17 Jan 2008 12:20:34 -0800 (PST) jml0...@yahoo.com wrote:
>
> | I have a Nordson hotmelt machine and it requires single phase 240 my
> | maintenance mechanic has it hooked up to a 3 phase 240 line and he
> | say's that will work fine. I have been having multiple electrical
> | problems with these machines and we have been unable to determine what
> | is the cause. Is it ok to leave 3 phase on single phase requirement?
>
> There would be 2 wires to the machine (plus EGC for protective ground).
> Probably no neutral. If the incoming power is 240 delta with a center
> tapped neutral on one side, connecting to the two phases that are 120
> volts relative to the neutral is just fine. If it is 208Y/120 then the
> machine is undervoltage and you'd be getting only about 75% of the heat
> you should get.
>
> What kinds of electrical problems are you having?
>
> --
> -----------------------------------------------------------------------------
> | Phil Howard KA9WGN |http://linuxhomepage.com/ http://ham.org/|
> | (first name) at ipal.net |http://phil.ipal.org/ http://ka9wgn.ham.org/|
> -----------------------------------------------------------------------------


I have replaced to main boards, 32 rtds ( thermal detections) and 1
whole machine
jmlpa

2008-01-18, 9:25 am

On Jan 18, 10:14 am, jmlpa <jml0...@yahoo.com> wrote:
> On Jan 17, 4:51 pm, phil-news-nos...@ipal.net wrote:
>
>
>
>
>
>
>
>
> I have replaced to main boards, 32 rtds ( thermal detections) and 1
> whole machine


3 rtds not 32
John G

2008-01-18, 5:25 pm


<jml0429@yahoo.com> wrote in message
news:c57ffe9d-97fb-4f97-8338-c14b0edd2cc0@k2g2000hse.googlegroups.com...
>I have a Nordson hotmelt machine and it requires single phase 240 my
> maintenance mechanic has it hooked up to a 3 phase 240 line and he
> say's that will work fine. I have been having multiple electrical
> problems with these machines and we have been unable to determine what
> is the cause. Is it ok to leave 3 phase on single phase requirement?


You did not give us much to go on.
So we can undestand your power system.
What country are you in?
What are the power specifications of the machine? Nameplate voltage,
Power and frequency.
What is the nature of the failures?

Simply put. Any 2 wires of a 3phase system will provide single phase
power. Of course the wireing has to be rated for the load and properly
protected.
But basicly your mechanic will be correct if all the numbers check out.

The important thing is the voltage supplied and the voltage required.

Please tell us some facts.
--
John G.