Home > Archive > Electrical code Compliance > March 2007 > UK electrical question
You are viewing an archived Text-only version of the thread.
To view this thread in it's original format and/or if you want to reply to
this thread please [click here]
| Author |
UK electrical question
|
|
| Stephen Temple 2007-03-27, 1:25 pm |
| I have some 2 core SY type cable. Is it permissible to use the wire
braid as an earth conductor, as in SWA type, or must 3 core with
green/yellow core be used to carry mains supplies?
--
Stephen Temple
J F Temple & Son Ltd
Mrs Temple's Cheese - Quality Norfolk Produce
Barn Owl Instruments and Controls
| |
| Andrew Gabriel 2007-03-28, 3:25 am |
| In article <130if3qsuo70v27@corp.supernews.com>,
Stephen Temple <usenet@jftemple.co.uk> writes:
> I have some 2 core SY type cable. Is it permissible to use the wire
> braid as an earth conductor, as in SWA type, or must 3 core with
> green/yellow core be used to carry mains supplies?
You would need to know what the effective cross-sectional area of
the braid is, to be sure it is sufficient for the protective
device in use. I just looked at one set of data, and that wasn't
specified. Alternatively, you could measure the earth fault loop
impedance (although it could vary from one sample to another) or
always ensure all supplies to such cables are RCD protected.
--
Andrew Gabriel
[email address is not usable -- followup in the newsgroup]
| |
| Stephen Temple 2007-03-28, 9:25 am |
| Andrew Gabriel wrote:
> In article <130if3qsuo70v27@corp.supernews.com>,
> Stephen Temple <usenet@jftemple.co.uk> writes:
>
> You would need to know what the effective cross-sectional area of
> the braid is, to be sure it is sufficient for the protective
> device in use. I just looked at one set of data, and that wasn't
> specified. Alternatively, you could measure the earth fault loop
> impedance (although it could vary from one sample to another) or
> always ensure all supplies to such cables are RCD protected.
>
Thanks. Again, in my data the braid cross section is not specified,
so some tests might be in order. Its difficult to ensure that a
portable appliance is always RCD protected, although everything at
our site is.
--
Stephen Temple
J F Temple & Son Ltd
Mrs Temple's Cheese - Quality Norfolk Produce
Barn Owl Instruments and Controls
|
|
|
|
|